Thermal Power up to 13kW
Monoblock
406% Output (COP 4,06)
Cooling and Heating function
Domestic water heating
OUTPUT | HEAT | kW | 13 | |
COOLING | kW | 9 | ||
COP | HEAT (A7/W35) | kW/kW | 4,06 | |
EER | COOLING | kW/kW | 3,05 | |
INPUT POWER | HEAT | kW | 3,2 | |
COOLING | kW | 2,95 | ||
SOUND POWER LEVEL | HEAT | dB(A) | 50 | |
POWER SUPPLY | V | 220 ~ 230 V | ||
COOLING AGENT | R410A | |||
DEFROST | AUTOMATICALY AT -5 C / EXTERNAL ENVIRONMENT TEMPERATURE | |||
OUTSIDE CASING MATERIAL | MATERIAL | GALVANISED, PAINTED STEEL (OPTIONAL STAINLESS STEEL 304L) | ||
ANTI CORROSION PROTECTION/AIR EXCHANGER | ANTI CORROSION PAINT | |||
DIMENSIONS | (WxDxH) | mm | 830 x 490 x 1160 | |
WEIGHT | kg | 106 / 113 | ||
HEAT EXCHANGER | MATERIAL | STAINLESS STEEL 316L | ||
COMPRESSOR TYPE | ROTARY | |||
AUXILIARY ELECTRIC HEATING | kW | 3,6,9 | ||
MAXIMUM WATER OUTLET TEMPERATURE WITHOUT AUXILIARY ELECTRIC HEATING | οC | 60οC | ||
WATER CIRCULATION PUMP | PRE-INSTALLED | WILO | ||
EXPANSION WATER TANK | PRE-INSTALLED | LIT | 8 | |
3-WAY VALVE DOMESTIC WATER HEATING & HEATING | OPTIONAL | |||
OPERATIONAL LIMITS | οC | HEATING: AMBIENT TEMP -20~43 DB ℃, DHW: AMBIENT TEMP. -20~43 DB ℃. | ||
INDICATIVE WORKING MODE | οC | HEATING : air temperature (DB / WB): 20oC / 15oC, water temperature ( input / output ): 15oC / 55oC. COOLING : air temperature (DB / WB): 35oC / 24oC, water temperature ( input / output ): 12oC / 7oC. |